General Purpose Relays
Safety Relay SR4 D/M
n 4 pole safety relay with either
2 NO+2 NC or 3 NO+1 NC contacts
n Forcibly guided contacts according to EN 50205
n Rated current 8 A
n Compact design & space efficient
Applications
Emergency shut-off, machine control, elevator and escalator
control, light barrier control
SCHRACK
F0244-C
Approvals
V Z T REG.-Nr. 40005334,
E214024,
968/EL 230.03/07
Technical data of approved types on request
Contact data
Contact configuration
Contact set
Type of interruption
Rated voltage / max. switching voltage AC
Rated current
Maximum breaking capacity AC
Contact material
Minimum contact load
Contact resistance
Rated frequency of operation with / without load
3 NO contacts and 1 NC contact
or
2 NO contacts and 2 NC contacts
single contact, forcibly guided
type A according to EN 50205
micro disconnection
250 / 400 VAC
8A
2000 VA
AgSnO2
10 mA / 5 V
w 100 mOhm / 1 A / 24 VDC
w 20 Ohm / 10 mA / 5 VDC
6 min-1 / 150 min-1
Contact ratings
Type Contact Load*)
Ambient
temp. [°C]
EN60947-5-1
SR4D/M 1 NO IEC 947-5-1 (AC15) utilization category 250 VAC / 3 A 23°C
SR4D/M 1 NO IEC 947-5-1 (DC13) utilization category 24 VDC / 3 A 23°C
*) load on one pole
Cycles
6,050
6,050
Coil data
Rated coil voltage range DC coil
5...110 VDC
Operative range to IEC 61810
2
Coil versions, DC-coil
Coil
Rated
Operate
Release
Coil
Rated coil
code
voltage
voltage
voltage
resistance
power
VDC
VDC
VDC
Ohm
mW
005
5
3.8
0.5
31+10%
806
006
6
4.5
0.6
45+10%
800
009
9
6.8
0.9
101+10%
802
012
12
9.0
1.2
180+10%
800
015
15
11.3
1.5
281+10%
801
018
18
13.5
1.8
405+10%
800
021
21
15.8
2.1
551+10%
800
024
24
18.0
2.4
720+10%
800
036
36
27.0
3.6
1620+10%
800
040
40
30.0
4.0
2000+10%
800
048
48
36.0
4.8
2880+10%
800
060
60
45.0
6.0
4500+10%
800
085
85
63.8
8.5
9031+10%
800
110
110
82.5
11.0
15125+10%
800
All figures are given for coil without preenergization, at ambient temperature +23°C
Other coil voltages on request
1
Datasheet Rev. IJ1
Dimensions are in mm unless Product specification
processing information only in the ‘Schrack’ section.
Issued 2009/10
otherwise specified and are
according to IEC 61810-1.
to be used together with the
www.tycoelectronics.com
shown for reference purposes Product data, technical para- 'Definitions' section in the cat- Specifications subject to
www.schrackrelays.com
only.
meters, test conditions and
alogue or at schrackrelays.com change.

Share Link: 

datasheetbank.com [ Privacy Policy ] [ Request Datasheet ] [ Contact Us ]