Sensor Accuracy & Field Calibration
CO2 ABC Logic Self Calibration
T8100-R sensors employ the patented ABC (Automatic
Background Calibration) Logic self-calibration system. ABC
Logic virtually eliminates the need for manual calibration
in applications where the indoor CO2 level drops to outside
levels during unoccupied periods (e.g. during evening hours).
ABC Logic is a special software routine in the sensor that
remembers the background readings for 14 consecutive
evenings, calculates if there is a sensor drift, and then
corrects for it.
With ABC Logic enabled, the sensor will typically reach its
operational accuracy after 25 hours of continuous operation
at a condition that is exposed to ambient reference levels.
Sensors will maintain accuracy specifications with ABC
Logic enabled, given that it is at least three times in 14 days
exposed to the reference value and this reference value is the
lowest concentration to which the sensor is exposed.
Note: Applies when used in typical indoor ambient air. Consult
Telaire if other gases or corrosive agents are part of the
application environment.
CO2 Calibration Guarantee
Telaire is serious about minimizing maintenance, so each
T8000-R sensor comes with a lifetime calibration guarantee.
Relay Settings
Switch #3
Switch #4
Down, Low
Down, Low
Down, Low
Up, High
Up, High
Up, High
Down, Low
Up, High
CO2 Relay Threshold and Hysteresis
Factory default setting
800 ppm, 100 ppm
1000 ppm, 100 ppm hysteresis
1200 ppm, 100 ppm hysteresis
1500 ppm, 100 ppm hysteresis
Note: Customizable settings available via UIP software
T2090.
Accessories
Enclosure Specifications
T1508 Aspiration Box for Duct Mounting
The Model 1508 is designed for in-duct sampling of
CO2 concentrations at flow rates greater than 400 fpm.
Clear cover allows for observation of the sensor. They
will accommodate any of the T8000-R series, and can
be used for temperature and RH when fitted. Enclosure
is screwed to the duct with probe inserted into air
stream. Air sampling probe is 1-inch (25.4mm) diameter
and 8-inch (203.2mm) long. Enclosure (ABS plastic)
has knockouts for conduit connection. Note: Wiring
penetrations must be sealed prior to use. CO2 sensor not
included.
T8100 standard enclosure
T8100-EC smaller Euro enclosure
T1508 Aspiration Box for Duct Mounting
T1505 Splash Resistant Enclosure
The Model 1505 is designed to protect the T8000-R series in
damp or wet environments as might occur in agricultural,
industrial or food processing environments. This enclosure
(ABS plastic) is designed to protect the sensor from dripping or
sprayed water. Any wall mount model of the T8000-R series
sensor can be installed inside the enclosure. The transparent
cover allows for viewing of the sensor/display. Four diffusion
ports allow for entry of CO2. Knockouts are provided for
conduit connection. Response time of the sensor is slowed to
approximately 30 minutes to measure a 90% step change in
concentrations. Enclosure is designed to screw directly to a
wall. CO2 sensor not included.