datasheetbank_Logo
Технический паспорт Поисковая и бесплатно техническое описание Скачать

AN34 Просмотр технического описания (PDF) - Cirrus Logic

Номер в каталоге
Компоненты Описание
Список матч
AN34 Datasheet PDF : 20 Pages
1 2 3 4 5 6 7 8 9 10 Next Last
T1/E1 Line Protection
Bellcore TR-NWT-001089
Bellcore Technical Reference TR-NWT-001089,
entitled "Electromagnetic Compatibility and
Electrical Safety Generic Criteria for Network
Telecommunications Equipment", contains re-
quirements for both inside and outside plant
network equipment and customer premises
equipment which will be used in a Regional Bell
Operating Company (RBOC) network. This
TR-NWT-001089 Type:
Section
Requirement
1234
2.4 ESD Immunity
XXXX
3.2 EMI
XXXX
4.5.3 NRTL Listing
XXXX
4.5.4
Short-Circuit Test
(Telecom Ports)
X
X
4.5.6
First-Level Lightning Surge
Test (Telecom Ports)
X
X
4.5.7
Second-Level Lightning Surge
Test (Telecom Ports)
X
X
4.5.8
Intra-Building Lightning Surge
Test (Telecom Ports)
X
X
X
X
4.5.9
AC Lightning Surge Test
(AC power Ports)
XXXX
4.5.10
Current Limiting Protector
Test (Telecom Ports)
X
XX
4.5.11
First-Level AC Power Fault
Test (Telecom Ports)
X
X
4.5.12
Second-Level AC Power Fault
Test (Telecom Ports)
X
Second-Level AC Power Fault
4.5.13 Test Series Equipment
X
(Telecom Ports)
4.5.14
Second-Level AC Power Fault
Test CPE (Telecom Ports)
X
X
Second-Level Intra-Building
4.5.15 AC Power Fault Test
X
(Telecom Ports)
5 Steady State Power Induction X
X
6 DC Potential Difference
X
X
7 Electrical Safety
XXXX
8 Corrosion
X
X
9 Bonding and Grounding
XXXX
Table 1. TR-NWT-001089 Requirements vs.
Equipment Type
document consolidates Electromagnetic Com-
patibility (EMC) and safety requirements found
in TR-NWT-000063, FR-NWT-000064 and TR-
TSY-000499. In all future issues of these
standards, EMC and safety criteria will be re-
placed by references to TR-NWT-001089.
Under TR-NWT-001089 telecommunications
equipment is classified into one of four type
categories based upon the nature of its connec-
tion to the network and intended operating
environment. Table 1 summarizes the major re-
quirements in TR-NWT-001089 which apply to
each equipment type. The following sections
summarize the lightning surge, AC power fault,
current limiting protector, and short-circuit tests
for telecommunications ports.
Lightning Immunity
TR-NWT-001089 has lightning immunity tests
for equipment installed on inside lines only (type
2 or 4 systems) and tests for equipment installed
on outside lines (type 1 or 3 systems). These
tests use the standard double exponential surge
waveform shown in Figure 1.
P
0.9P
(PEAK VALUE)
0.5P
FRONT TIME = 1.25 (b-a) = T1 - T0
DURATION = (T2 - T0 )
0.1P
T0 a
b T1
T2
TIME
Figure 1. Double Exponential Surge Waveform
4
AN34REV1

Share Link: 