1 2 3
HFE1600 Series
Model Selector
Model
Output
Voltage
Adjust
Range(1)
HFE1600-12
HFE1600-12/S
HFE1600-24
HFE1600-24/S
HFE1600-32
HFE1600-32/S
HFE1600-48
HFE1600-48/S
Model
12V
12V
24V
24V
32V
32V
48V
48V
Load
Reg
9.6 - 13.2V
9.6 - 13.2V
19.2 - 29V
19.2 - 29V
25.6 - 38.4V
25.6 - 38.4V
38.4 - 58V
38.4 - 58V
Line
Reg
HFE1600-12
60mV
30mV
HFE1600-12/S
60mV
30mV
HFE1600-24
120mV
60mV
HFE1600-24/S 120mV
60mV
HFE1600-32
160mV
80mV
HFE1600-32/S 160mV
80mV
HFE1600-48
240mV
120mV
HFE1600-48/S 240mV
120mV
(4) At 75% load, 100 / 230VAC input
Max Current
(Vin>170VAC)
133A
133A
67A
67A
47A
47A
33A
33A
Ripple &
Noise(1)
240mV
240mV
240mV
240mV
320mV
320mV
480mV
480mV
Max Power
(Vin>170VAC)
1596W
1596W
1608W
1608W
1500W
1500W
1584W
1584W
Efciency
(%)(4)
87 / 90%
87 / 90%
88 / 90%
88 / 90%
88 / 90%
88 / 90%
89 / 92%
89 / 92%
Max Current
(100<Vin<170VAC)(2)
100A
100A
50A
50A
37.5A
37.5A
25A
25A
I2C
-
Yes
-
Yes
-
Yes
-
Yes
Max Power
(100<Vin<170VAC)(2)
1200W
1200W
1200W
1200W
1200W
1200W
1200W
1200W
Accessories
Model
HFE1600-S1U
HFE1600-S1U-TB
HFE1600/BP
HFE/C15U
HFE1600-D1U
HFE1600-D1U-TB
Description
Five slot 19” rack, IEC320-C16 input connectors (5)
Five slot 19” rack, Terminal Block input connectors (5)
One slot blanking panel, four provided with each rack
AC Power cord, 2.0m long, one per power supply required
Four slot (two isolated pairs), dual output 19” rack, IEC320 input
Four slot (two isolated pairs), dual output 19” rack, terminal block input
Maximum Rack Current
266A each side (532A total)
266A each side (532A total)
-
-
266A each side (532A total)
266A each side (532A total)
Outline HFE1600
FRONT VIEW
85.0 ±0.5
21.4
42.2
SEE NOTE 2
POWER SUPPLY LOCKING
86.2 ±0.5
REAR VIEW
Outline HFE1600S1U
M5 HOLES FOR
MOUNTING BRACKETS.
4 PLACES
(SEE NOTE 3.)
14.0 TYPx2
OUTPUT
BUS BAR " -V "
PMBUS ADRESS
SEE NOTE 4.
74.0
55.0
20.0 TYPx2
290.0
236.6
55.0
80.5
OUTPUT
BUS BAR " -V "
OUTPUT
BUS BAR " +V "
OUTPUT
BUS BAR " +V "
13.0 TYPx2
13.0 TYPx2
MODULE " A " MODULE " B " MODULE " C "
SEE NOTE 2.
MODULE " D "
MODULE " E "
114.0
12V 24V 32V 48V
12V 24V 32V 48V
12V 24V 32V 48V
12V 24V 32V 48V
12V 24V 32V 48V
MODEL KEY
FOR DIFFERENT
OUTPUT VOLTAGE MODELS.
A
43.0
43.0
320.4 ±1.0
311.0 ±1.0
300.0 ±0.5
IN/OUT CONNECTOR
SEE NOTE 1.
MOUNTING HOLES M4
MARKED "A"
2 HOLES ON EACH SIDE.
252.0 ±0.5
9.4
A
HOLES FOR
BLANK PANEL
MOUNTING.
USE FLAT HEAD
SCREW M3x6
10 PLACES
MARKED "A"
A
NOTES
1. MOUNTING HOLES FOR RACK 19". USE M6x12 SCREWS TO FIX THE
UNIT TO A RACK.
2. USE NUT,FLAT WASHER AND SPRING WASHER FOR LOAD WIRES
FIXING. USE M6 LUG FOR LOAD WIRES.RECOMMENDED
TORQUE: 42-56 Kgf.cm
3. TO FIX THE MOUNTING BRACKET TO THE CHASSIS USE M5x10 SEMS
SCREWS .RECOMMENDED TIGHTENING TORQUE 27~31Kgf.cm.
SCREWS MUST NOT PENETRATE THE CHASSIS MORE THAN 6.0 mm.
4. REFER TO INSTRUCTION MANUAL FOR SETTING DETAILS.
5. MODEL NAME, VOLTAGE AND CURRENT RATING AND SAFETY
APPROVALS SYMBOLS WILL BE SHOWN HERE ACCORDING TO
THE SPECIFICATION.
A
A
A
A
445.0 ±1.0
483.0 ±1.0
SEE NOTE 1.
466.2 ±0.5
6. THE HFE-S1U RACK IS SHOWN WITH 5 HFE1600
UNITS INSTALLED.
For Additional Information, please visit
us.tdk-lambda.com/lp/products/hfe-series.htm
1-800-526-2324 • www.us.tdk-lambda.com/lp/
56
Revision B4: Oct 2013

Share Link: 