Level 2 Mode
r-l
lcl
spru
m
sprt
0
lba
0
mU-s
0.0
mU-e
0.0
ol-h
105.0
ol-l
-5.0
orl
0.0
inf
0
alh1
0.02
alh2
0.02
insh
0.0
insl
0.0
Remote/Local
Used for the communications function.
SP Ramp Time Unit
SP Ramp Set Value
LBA Detection Time
Available only when the LBA (loop break alarm) function of the Controller is selected.
MV at Stop
MV at PV Error
MV Upper Limit
MV Lower Limit
MV Change Rate Limit
Input Digital Filter
Alarm 1 Hysteresis
Available only when the Controller has an alarm output.
Alarm 2 Hysteresis
Available only when the Controller has an alarm output.
Input Shift Upper Limit
Available if the input type connected to the Controller is a thermocouple or platinum resistance
thermometer.
Input Shift Lower Limit
Available if the input type connected to the Controller is a thermocouple or platinum resistance
thermometer.
I-76
Digital Controller E5CK