datasheetbank_Logo
Технический паспорт Поисковая и бесплатно техническое описание Скачать

RM24150 Просмотр технического описания (PDF) - C and D TECHNOLOGIES

Номер в каталоге
Компоненты Описание
Список матч
RM24150
CD-Technologies
C and D TECHNOLOGIES CD-Technologies
RM24150 Datasheet PDF : 4 Pages
1 2 3 4
Input Specifications
Parameter
Operating Range
Current
Efficiency
Power Factor Correction (PFC)
Conditions
45 - 65 Hz, single phase, no taps required
Adjustable
Min
183
Typ
Max
264
27
>85
>.99
Units
VAC
A
%
MEASUREMENTS OF RM24150
Module
Weight
25 lbs.
Height
7U (12.25)
Depth
15.25
Width
5.1
Shelf*
Weight
Height
Depth
Width
18 lbs.
7U (12.25)
15..25maximum
23rack mount
*These measurements are specifically for the 600A Power Shelf for up to 4 quantity RM24150.
Please consult factory for other shelf and power plant options.
GENERAL FEATURES
Hot Swappable Modules
These shelf-mounted modules are easy and safe to install
or remove while system is operational without affecting
the overall systems performance.
Parallel Operation and Automatic Load Sharing
Forced or passive load sharing is available between
modules of the same operating voltages in parallel
applications.
Current Limit
The Current Limit is adjustable between 0A to 150A. Upon
exceeding this limit, the rectifier automatically reduces
output voltage.
Safety
UL/CUL Recognized: UL 1950/CSA 950
File Number: E181908.
Alarm Outputs
Rectifier Fail Alarm
Thermal Shutdown Occurring
Open Sense Lead Has Occurred
AC Power Has Failed Alarm
DC Breaker Is Open Alarm
AC Breaker Is Open Alarm
(RFA)
(THSD)
(OS)
(ACF)
(DCBKR)
(ACBKR)
Note: All alarms are Form Arelay type contacts
Control Inputs
High Voltage Shutdown
Restart
Equalize
Temporary Restraint
Emergency Shutdown
} (HVSD)
(RS)
(EQ)
All control inputs
are initiated with
a ground closure
(TR)
(EMSD) }
24VAC voltage
reference to
ground
Page 2
A4RM24150 5/98 REV A

Share Link: 

datasheetbank.com [ Privacy Policy ] [ Request Datasheet ] [ Contact Us ]